GCK low voltage draw-out switch cabinet consists of power distribution center cabinet (PC) and motor control center (MCC), which applies to power distribution system that AC 50Hz, maximum operating current to 4000A in power station, substation, industrial and mining enterprises and other electric power users, to be used as power distribution, motor control and lighting and electric energy switching, distribution and control for other power distribution equipments.
This series of products have advantages, such as high breaking capacity, good heat stability, advanced and reliable structure, electrical appliance scheme is suitable to actual series, strong universality, combine any scheme at will, one cabinet body holding more loops, saving floor area, good-looking appearance, high protective level, safe and reliable, convenient for maintenance and other advantages.
This product conforms to IEC60439, GB7251.1, ZBK3600 and other standards.
Features of main structures:
1、The framework adopts profiled bar and uses three-dimensional angle plate for positioning, and the bolted connection is without welding structure, so that avoid the welding deformation and stress, improve installation accuracy. It also can use 8MF section bar;
2、The installing hole of framework and parts changes with module E=20mm, and the assembly is flexible;
3、The interior structural parts are color zinc-plated. The outside adopts static epoxy powder for spraying after acid pickling and phosphating treatment;
4、The functional unit of drawer and door has mechanical interlocking through the operating mechanism of master switch. Master switch cannot be opened in switch-on position. The operating mechanism may be locked in swich-on or switch-off position by means of adding padlock outside. Among compartment of function unit has metal plate for separation, the drawer has good interchangeability, as well as has three positions including operation, test and separation.
Basic specifications:
Project |
unit |
parameter |
||
rated voltage of main circuit |
V |
AC380(400)、(660) |
||
rated voltage of auxiliary circuit |
V |
AC220、380(400);DC110、220 |
||
rated frequency |
Hz |
50(60) |
||
rated insulation voltage |
V |
660(1000) |
||
maximum capacity of control motor |
kW |
155 |
||
rated current |
horizontal bus |
A |
≤4000 |
|
vertical bus(MCC) |
600、800、1000 |
|||
connector clip for contact of main circuit |
200、400 |
|||
connector clip for contact of auxiliary circuit |
16 |
|||
rated short-time withstand current of bus bar |
kA/1s |
30、50 |
||
rated peak withstand current of bus bar |
kA/0.1s |
63、105 |
||
power frequency test voltage |
main circuit |
V/1min |
2500 |
|
auxiliary circuit |
2000 |
|||
busbar |
three-phase four-wire system |
|
A、B、C、PEN |
|
three-phase five-wire system |
|
A、B、C、PE、N |
||
protection level |
|
IP30 |